TEK

Features

● Max circuit length 3658 m
● Tmax maintain 101°C
● Up to 750 Vac

More information:

Description

Thermon TEK constant wattage resistance heating cables are used for temperature maintenance of long pipe lengths up to 101°C or for freeze protection where circuit lengths exceed the limitations of parallel resistance heating cables and high maintenance temperatures or high temperature exposure are required. Circuit lengths up to 3658 meters can be powered from a single power point. TEK’s series connection ensures consistent power output over the entire length of the cable without voltage loss in parallel tracer constructions.

The TEK heat tracing cables are certified for use in regular (non-classified) areas and in potentially explosive environments.

Features

  • Pipe freeze protection and temperature maintenance up to 101°C
  • Maximum exposure temperature of 250°C
  • Circuit lengths of up to 3658 meters
  • Rated up to 750 Vac
  • Metallic braid for grounding purposes
  • Fluoropolymer (FOJ) overjacket
  • Available with 2 or 3 conductors
  • Worldwide approvals

Product variants

SKU P/N Item Conductors Resistance per conductor @ 20°C Conductor size Overjacket
TEK 2C40 2 0.01492 Ω/m 16 AWG Fluoropolymer
TEK 2C50 2 0.009449 Ω/m 14 AWG Fluoropolymer
TEK 2C60 2 0.005945 Ω/m 12 AWG Fluoropolymer
TEK 2C70 2 0.003478 Ω/m 10 AWG Fluoropolymer
2003-005 21209 TEK 3C40 3 0.01492 Ω/m 16 AWG Fluoropolymer
2003-006 21219 TEK 3C50 3 0.009449 Ω/m 14 AWG Fluoropolymer
2003-007 21227 TEK 3C60 3 0.005945 Ω/m 12 AWG Fluoropolymer
2003-008 20989 TEK 3C70 3 0.003478 Ω/m 10 AWG Fluoropolymer

THERMON-DS-TEK-TEP0021U-0917.PDF

Datasheet

Additional information

Rated voltage

Up to 750 Vac

Max. maintenance temperature

101°C

Max. exposure temperature

Continuous (power-off): 250°C

Min. installation temperature

-60°C

Min. bend radius

22 mm @ -15°C
32 mm @ -60°C

T-rating

T2 to T6
Using the principles of stabilized design or limiters