VSX-HT

Features

● 15, 32, 48 & 64 W/m @ 10°C
● Tmax maintain 200°C
● 110-120 or 208-277 Vac

More information:

Description

Thermon VSX-HT self-regulating heat tracing cables are tailored for process temperature maintenance and freeze protection applications demanding high maintain temperatures or exposures.

The heat output of VSX-HT heat trace cables adjusts dynamically along the entire circuit, responding to surrounding conditions. As heat loss increases due to a drop in ambient temperature, the cable intensifies its heat output. Conversely, when heat loss decreases (due to a rise in ambient temperature or product flow), the cable reduces its heat output. VSX-HT heat tracing cables come equipped with a fluoropolymer (OJ) overjacket, providing superior chemical resistance against aggressive organics and corrosives.

Approved for use in ordinary (nonclassified) areas, hazardous (classified) areas, and Zone 1, 2, 21, and 22 areas, VSX-HT heat trace cables offer versatile and reliable solutions across various environments.

Features

  • Pipe freeze protection and temperature maintenance up to 200°C
  • Safe and efficient in operation, uniform pipe temperatures and energy saving technology
  • Semiconductive self-regulating heating matrix allows for overlaps without overheating
  • Withstands temperatures associated with steam purging
  • Cut-to-length parallel circuitry
  • Nickel-plated copper bus wires
  • Metallic braid for grounding purposes
  • Available voltages 110-120 or 208-277 Vac
  • Unique monolithic co-extrusion processing for optimal performance
  • Compatible with user-friendly and easy to install Thermon components

Product variants

SKU P/N Item Power output Voltage (Vac) Overjacket
2000-049 27912 VSX-HT 5-2-OJ 9 W/m @ 10°C, 230 Vac 208-277 Fluoropolymer
2000-045 27902 VSX-HT 5-1-OJ 16 W/m @ 10°C, 120 Vac 110-120 Fluoropolymer
2000-050 27932 VSX-HT 10-2-OJ 32 W/m @ 10°C, 230 Vac 208-277 Fluoropolymer
2000-046 27922 VSX-HT 10-1-OJ 33 W/m @ 10°C, 120 Vac 110-120 Fluoropolymer
2000-051 27952 VSX-HT 15-2-OJ 48 W/m @ 10°C, 230 Vac 208-277 Fluoropolymer
2000-047 27942 VSX-HT 15-1-OJ 49 W/m @ 10°C, 120 Vac 110-120 Fluoropolymer
2000-052 27972 VSX-HT 20-2-OJ 64 W/m @ 10°C, 230 Vac 208-277 Fluoropolymer
2000-048 27962 VSX-HT 20-1-OJ 66 W/m @ 10°C, 120 Vac 110-120 Fluoropolymer

THERMON-DS-VSX-HT-TEP0208U-0218.pdf

Datasheet

Additional information

Available watt densities

15, 32, 48, 64 W/m @ 10°C

Nominal supply voltage

110-120 or 208-277 Vac

Max. maintenance temperature

200°C

Max. exposure temperature

Intermittent (power-on or off): 250°C

Min. installation temperature

-60°C

Min. bend radius

10 mm @ -15°C
32 mm @ -60°C

T-rating

15 and 32 W/m: T3/T200°C
48 and 64 W/m: T2/230°C

Based on stabilized design: T2 to T6