More information:
Description
Thermon VSX-HT self-regulating heat tracing cables are tailored for process temperature maintenance and freeze protection applications demanding high maintain temperatures or exposures.
The heat output of VSX-HT heat trace cables adjusts dynamically along the entire circuit, responding to surrounding conditions. As heat loss increases due to a drop in ambient temperature, the cable intensifies its heat output. Conversely, when heat loss decreases (due to a rise in ambient temperature or product flow), the cable reduces its heat output. VSX-HT heat tracing cables come equipped with a fluoropolymer (OJ) overjacket, providing superior chemical resistance against aggressive organics and corrosives.
Approved for use in ordinary (nonclassified) areas, hazardous (classified) areas, and Zone 1, 2, 21, and 22 areas, VSX-HT heat trace cables offer versatile and reliable solutions across various environments.
Features
- Pipe freeze protection and temperature maintenance up to 200°C
- Safe and efficient in operation, uniform pipe temperatures and energy saving technology
- Semiconductive self-regulating heating matrix allows for overlaps without overheating
- Withstands temperatures associated with steam purging
- Cut-to-length parallel circuitry
- Nickel-plated copper bus wires
- Metallic braid for grounding purposes
- Available voltages 110-120 or 208-277 Vac
- Unique monolithic co-extrusion processing for optimal performance
- Compatible with user-friendly and easy to install Thermon components
Product variants
SKU | P/N | Item | Power output | Voltage (Vac) | Overjacket |
2000-049 | 27912 | VSX-HT 5-2-OJ | 9 W/m @ 10°C, 230 Vac | 208-277 | Fluoropolymer |
2000-045 | 27902 | VSX-HT 5-1-OJ | 16 W/m @ 10°C, 120 Vac | 110-120 | Fluoropolymer |
2000-050 | 27932 | VSX-HT 10-2-OJ | 32 W/m @ 10°C, 230 Vac | 208-277 | Fluoropolymer |
2000-046 | 27922 | VSX-HT 10-1-OJ | 33 W/m @ 10°C, 120 Vac | 110-120 | Fluoropolymer |
2000-051 | 27952 | VSX-HT 15-2-OJ | 48 W/m @ 10°C, 230 Vac | 208-277 | Fluoropolymer |
2000-047 | 27942 | VSX-HT 15-1-OJ | 49 W/m @ 10°C, 120 Vac | 110-120 | Fluoropolymer |
2000-052 | 27972 | VSX-HT 20-2-OJ | 64 W/m @ 10°C, 230 Vac | 208-277 | Fluoropolymer |
2000-048 | 27962 | VSX-HT 20-1-OJ | 66 W/m @ 10°C, 120 Vac | 110-120 | Fluoropolymer |
THERMON-DS-VSX-HT-TEP0208U-0218.pdf
Datasheet
Additional information
Available watt densities | 15, 32, 48, 64 W/m @ 10°C |
---|---|
Nominal supply voltage | 110-120 or 208-277 Vac |
Max. maintenance temperature | 200°C |
Max. exposure temperature | Intermittent (power-on or off): 250°C |
Min. installation temperature | -60°C |
Min. bend radius | 10 mm @ -15°C |
T-rating | 15 and 32 W/m: T3/T200°C Based on stabilized design: T2 to T6 |