TubeTrace with HPT

Features

● 16, 33, 49, 66 W/m @ 10°C
● Tmax maintain 204°C
● Cut to length

More information:

Description

Thermon TubeTrace, featuring the “cut-to-length” HPT power-limiting heat tracing, is crafted to offer freeze protection or temperature maintenance within the range of 5°C to 177°C for tubing with high-temperature exposure requirements. HPT demonstrates resilience to temperature exposures of up to 260°C.

The composite structure incorporating the heating element and fiber substrate, along with an additional fiber cushion layer, contributes to HPT’s exceptional durability as a heating cable. This durability has established TubeTrace with HPT as the industry standard for high-temperature applications in emissions and process analyzers.

Features

  • Uniform watt density per unit length
  • Avoids high inrush current during startup
  • Eliminates the requirement for oversized circuit breakers
  • Approved for use in hazardous (classified) areas
  • Long circuit lengths possible

THERMON-DS-TUBETRACE-HPT-CLX0016U-0714.PDF

Datasheet

Additional information

Available watt densities

16, 33, 49, 66 W/m @ 10°C

Supply voltages

120 to 240 Vac nominal

Tube temperature range

5°C to 204°C

Max. continuous exposure temperature

260°C (power-off)