TC1 & TC-1/XP Plus

Features

● Mechanical thermostat
● Pipe or wall mounting
● Surface sensing

More information:

Description

The Thermon TC1 and TC1/XP Plus mechanical thermostats serve as adjustable control thermostats designed for freeze protection and temperature maintenance applications, specifically tailored for pipewall or tankwall sensing. With three temperature control and bulb exposure ranges, these thermostats offer versatility to meet varying heating requirements.

The TC1 is crafted for wall mounting, with the option for pipe mounting using the separate Thermon XP-1 stainless steel mounting bracket. It features PVC-coated galvanized steel flexible capillary armoring, complete with a capillary gland and insulation entry device.

On the other hand, the TC1/XP Plus variant streamlines installation with an expediter, facilitating direct attachment to the pipe and allowing a single heating cable to enter and connect within the enclosure. Transparent covers provide visibility for indicating lamps, indicating power-on and heater-on status. Both thermostats are housed in nonmetallic enclosures, ensuring durability in harsh industrial environments and providing watertight and dust-tight protection according to IP65 standards. The external hardware is constructed from stainless steel.

Compliant with requirements for nonhazardous locations, the TC1 and TC1/XP Plus thermostats offer a reliable solution for a wide range of industrial heating applications.

Product variants

SKU P/N Item Control range Control differential Max. bulb exposure temp. Mounting type
2023-016 40-441.501.004 TC1-1-60 -15°C to +60°C ±4°C 150°C Wall
2023-019 17397 TC1-1-120 +20°C to +120°C ±4°C 145°C Wall
2023-027 40-441.811.104 TC1-1-300 +50°C to +300°C ±10°C 320°C Wall
2023-028 40-441.814.104 TC1/XP Plus-1-60 -15°C to +60°C ±4°C 150°C Pipe
2023-029 40-441.816.104 TC1/XP Plus-1-120 +20°C to +120°C ±4°C 145°C Pipe

THERMON-DS-TC1-TC1-XP-PLUS-TEP0055U-0113.PDF

Datasheet

Additional information

Voltage rating

400 Vac

Switch rating

230 Vac = 16 A (Ohmic, NC contact)
400 Vac = 10 A (Ohmic, NC contact)

Operating ambient temperature

-30°C to +55°C

Electrical connection

Terminal block

Adjustable control range

TC1-1-60 = -15° to +60° C
TC1-1-120 = 20°C to 120°C
TC1-1-300 = 50°C to 300°C

Max. control differential

TC1-1-60 = ±4°C
TC1-1-120 = ±4°C
TC1-1-300 = ±10°C

Max. bulb exposure temperature

TC1-1-60 = 50°C
TC1-1-120 = 145°C
TC1-1-300 = 320°C

Bulb dimensions/material/capillary length

TC1-1-60 = 6 x 140 mm/stainless steel/1 m
TC1-1-120 = 6 x 140 mm/stainless steel/1 m
TC1-1-300 = 4 x 165 mm/stainless steel/1 m

Approximate weight

1.5 kg