More information:
Description
Thermon MIS high performance mineral heating cables are used extensively for high temperature maintenance up to 500°C, high temperature exposure and/or high watt density applications which exceed the limitations of thermoplastic insulated cables. MIS mineral insulated cables have a Stainless Steel 321 outer sheath to meet the temperature and exposure requirements of the application.
MIS cables are approved for use in ordinary (non-classified) areas and are certified to the ATEX directive for use as Zone 1 and 2 classified products.
Features
- Pipe freeze protection and temperature maintenance up to 500°C
- Stainless Steel 321 sheath material
- Allows cable to be installed at temperatures to -55°C
- Corrosion resistance and high resistance to mechanical abuse
- High performance output
MIS HEATER SETS
Thermon MIS/MIQ cable sets are available in various factory fabricated configurations designed for the cable type and number of conductors. The standard assemblies consists of standard 1 meter (other lengths optional) non-heating cold leads with 200 mm long insulated pigtails.
Product variants
SKU | P/N | Item | Resistance @ 20°C | Nominal diameter | Voltage | Construction | Min cold lead |
2005-010 | 40-416.510.000 | MIS-M1-10K | 10000 Ω/km | 3.2 mm | 800 Vac | Single core | 2.5 mm² |
2005-009 | 40-416.506.300 | MIS-M1-6300 | 6300 Ω/km | 3.2 mm | 800 Vac | Single core | 2.5 mm² |
2005-008 | 40-416.504.000 | MIS-M1-4000 | 4000 Ω/km | 3.2 mm | 800 Vac | Single core | 2.5 mm² |
2005-007 | 40-416.502.500 | MIS-M1-2500 | 2500 Ω/km | 3.6 mm | 800 Vac | Single core | 2.5 mm² |
2005-006 | 40-416.501.600 | MIS-M1-1600 | 1600 Ω/km | 3.8 mm | 800 Vac | Single core | 6.0 mm² |
2005-005 | 40-416.501.000 | MIS-M1-1000 | 1000 Ω/km | 4.1 mm | 800 Vac | Single core | 6.0 mm² |
2005-004 | 40-416.500.630 | MIS-M1-630 | 630 Ω/km | 4.5 mm | 800 Vac | Single core | 2.5 mm² |
2005-003 | 40-416.500.400 | MIS-M1-400 | 400 Ω/km | 5.0 mm | 800 Vac | Single core | 2.5 mm² |
2005-002 | 40-416.500.250 | MIS-M1-250 | 250 Ω/km | 5.6 mm | 800 Vac | Single core | 6.0 mm² |
2005-001 | 40-416.500.160 | MIS-M1-160 | 160 Ω/km | 6.5 mm | 800 Vac | Single core | 6.0 mm² |
THERMON-DS-EN-GB-MIS-MIQ.PDF
Datasheet
Additional information
Rated voltage | 800 Vac |
---|---|
Max. maintain temperature | 500°C |
Max. exposure temperature | Continuous (power-off): 800°C |
Max. watt density | 250 W/m |
Min. installation temperature | -55°C |
Min. bend radius | 5x cable O.D. |
T-rating | T1 to T6 |
Connections | Laser welded leads |