KSX

Features

● 15, 32, 48 & 64 W/m @ 10°C
● Tmax maintain 121°C
● 230 Vac

More information:

Description

Thermon’s high-performance KSX self-regulating trace heating cables are meticulously designed for demanding freeze protection applications or process temperature maintenance up to 150°C, specifically where steam cleaning is unnecessary.

The heat output of KSX heating cables dynamically adjusts along the entire circuit in response to surrounding conditions. As heat loss increases due to a drop in ambient temperature, the cable intensifies its heat output. Conversely, when heat loss decreases (due to a rise in ambient temperature or product flow), the cable responds by reducing its heat output. KSX heat tracing cables come with a fluoropolymer (OJ) overjacket, ensuring superior chemical resistance against aggressive organics and corrosives.

Certified for use in ordinary (nonclassified) areas and potentially explosive atmospheres in line with the ATEX Directive and the IECEx Scheme, KSX heat trace cables offer reliable solutions across diverse environments.

Features

  • Pipe freeze protection and temperature maintenance up to 121°C
  • Safe and efficient in operation, uniform pipe temperatures and energy saving technology
  • Semiconductive self-regulating heating matrix allows for overlaps without overheating
  • Cut-to-length parallel circuitry
  • Nickel-plated copper bus wires
  • Metallic braid for grounding purposes
  • Available voltage 230 Vac
  • Meter markings on overjacket
  • Compatible with user-friendly and easy to install Thermon components

Product variants

SKU P/N Item Power output Voltage (Vac) Overjacket
2000-065 25512 KSX 5-2-OJ 15 W/m @ 10°C, 230 Vac 230 Fluoropolymer
2000-066 25532 KSX 10-2-OJ 32 W/m @ 10°C, 230 Vac 230 Fluoropolymer
2000-067 25552 KSX 15-2-OJ 48 W/m @ 10°C, 230 Vac 230 Fluoropolymer
2000-068 25572 KSX 20-2-OJ 64 W/m @ 10°C, 230 Vac 230 Fluoropolymer

THERMON-DS-KSX-TEP0072U-0721.PDF

Datasheet

Additional information

Available watt densities

15, 32, 48, 64 W/m @ 10°C

Nominal supply voltage

230 Vac

Max. maintenance temperature

Continuous (power-on): 121°C

Max. exposure temperature

Continuous (power-on): 121°C

Min. installation temperature

-60°C

Min. bend radius

10 mm @ -15°C
32 mm @ -60°C

T-rating

Based on stabilized design: T3 to T6