Thermon FP parallel resistance constant wattage heating cables are designed for freeze protection and process temperature maintenance, supporting temperatures up to 65°C. Suitable for installation on piping, tanks, vessels, and equipment, FP heating cables demonstrate resilience with continuous exposure temperatures of up to 204°C when powered off. All FP heating cables come with a fluoropolymer (OJ) overjacket, providing robust chemical resistance against aggressive organics and corrosives.
The parallel resistance configuration allows easy field termination and customization with user-friendly Thermon kits. FP heat trace cables deliver consistent and reliable heat outputs across various circuit lengths, without the inrush current associated with self-regulating heating cables. This eliminates the need for oversizing power distribution equipment.
Approved for use in ordinary (nonclassified) areas, hazardous (classified) areas, and Zone 2 classified areas, FP heating cables offer versatile and dependable solutions for diverse environments.
Features
- Pipe freeze protection and temperature maintenance up to 65°C
- Maximum exposure temperature of 204°C
- Extended circuit lengths of up to 399 meters
- Available service voltages 120, 240, 400 and 575 Vac
- Cut-to-length parallel circuitry
- Nichrome heating element
- 4 mm² copper bus wires
- Metallic braid for grounding purposes
- Fluoropolymer (OJ) overjacket
- Worldwide approvals
- Compatible with user-friendly and easy to install Thermon components
Product variants
SKU | P/N | Item | Power output | Zone length | Voltage (Vac) | Outer jacket |
2002-001 | 22332 | FP 2.5-2-OJ | 8 W/m, 230 Vac | 137 cm | 230-240 | Fluoropolymer |
2002-006 | – | FP 2.5-1-OJ | 8 W/m, 120 Vac | 76 cm | 120 | Fluoropolymer |
2002-002 | 22342 | FP 5-2-OJ | 15 W/m, 230 Vac | 102 cm | 230-240 | Fluoropolymer |
2002-007 | – | FP 5-1-OJ | 16 W/m, 120 Vac | 61 cm | 120 | Fluoropolymer |
2002-003 | 22387 | FP 8-2-OJ | 24 W/m, 230 Vac | 102 cm | 230 | Fluoropolymer |
2002-008 | – | FP 8-4-OJ | 18 W/m, 400 Vac | 152 cm | 400 | Fluoropolymer |
2002-004 | 22352 | FP 10-2-OJ | 33 W/m, 230 Vac | 76 cm | 230-240 | Fluoropolymer |
2002-009 | – | FP 10-1-OJ | 33 W/m, 120 Vac | 61 cm | 120 | Fluoropolymer |
2002-005 | 22362 | FP 10-4-OJ | 23 W/m, 400 Vac | 137 cm | 400 | Fluoropolymer |
2002-010 | – | FP 10-5-OJ | 33 W/m, 575 Vac | 168 cm | 575 | Fluoropolymer |
THERMON-DS-FP-TEP0016U-0113.PDF
Datasheet
Additional information
Max. watt density | 33 W/m |
---|---|
Max. operating voltage | 690 Vac |
Max. maintenance temperature | 65°C |
Max. exposure temperature | Continuous (power-off): 200°C |
Min. installation temperature | -60°C |
Min. bend radius | 10 mm @ -15°C |
T-rating | Based on stabilized design: T3 to T6 |