IS-KTeS

Features

● Tmax 260°C
● Approx. 20 W/m
● IP65

More information:

Description

Isopad IS-KTeS is a preterminated heating cable featuring PTFE insulation, suitable for environments where no excessive mechanical loads are expected, and moisture may be present.

This cable is known for its flexibility and easy installation, providing cost-effective and versatile heating solutions. Applications include heat tracing for pipes, small containers, tools, machines, extremely thin and short pipes, as well as machine parts with limited mounting space.

PRODUCT VARIANTS

SKU P/N Item Length ⁽¹⁾ Voltage Rating ⁽²⁾
2100-001 680108-000 IS-KTES/2.2M/230V/50W/KE1.5M 2.20 m 230 V 50 W
2100-002 970664-000 IS-KTES/4.4M/230V/100W/KE1.5M 4.40 m 230 V 100 W
2100-003 414978-000 IS-KTES/7.0M/230V/140W/KE1.5M 7.00 m 230 V 140 W
2100-004 869130-000 IS-KTES/11.0M/230V/250W/KE1.5M 11.00 m 230 V 250 W
2100-005 037962-000 IS-KTES/16.0M/230V/330W/KE1.5M 16.00 m 230 V 330 W
2100-006 927424-000 IS-KTES/22.0M/230V/500W/KE1.5M 22.00 m 230 V 500 W
2100-007 073216-000 IS-KTES/28.0M/230V/630W/KE1.5M 28.00 m 230 V 630 W
2100-008 206840-000 IS-KTES/40.0M/230V/920W/KE1.5M 40.00 m 230 V 920 W
2100-009 736072-000 IS-KTES/58.0M/230V/1300W/KE1.5M 58.00 m 230 V 1300 W
2100-010 380470-000 IS-KTES/80.0M/230V/1740W/KE1.5M 80.00 m 230 V 1740 W
2100-011 480964-000 IS-KTES/112.0M/230V/2360W/KE1.5M 112.00 m 230 V 2360 W
2100-012 335974-000 IS-KTES/156.0M/230V/3391W/KE1.5M 156.00 m 230 V 3391 W

Other lengths and power specifications, etc. available on request.

⁽¹⁾ Tolerances ± (2% + 100 mm)
⁽²⁾ Tolerances ±10%

Additional information

Area classification

Nonhazardous, ordinary area

Ingress protection

IP65

Electrical protection class

Class I

Max. withstand temperature (power off)

260°C

Max. withstand temperature (power on)

Depends upon power

Outer diameter (OD)

2.5 to 3.5 mm

Type

Resistance heating cable

Material

Various alloys

Material of insulation

PTFE

Material of outer sheath

Copper-nickel braid

Connection length

Terminated at each end with a 1.5 m cold lead

Cross section

1.0 mm2

Insulation material

PTFE

Frequency

50-60 Hz

Nominal operating voltage

230 Vac

Power per meter

20 W/m

Max. operating temperature

260°C

Min. bend radius

10 mm

Minimum spacing

5 mm